Ask a candidate what the glycol percentage in their loop should be. Someone who has run a direct-to-chip system will say about 25%, and may tell you the acceptable band is 24.5 to 27.5%. Someone who has only read about it usually can't give a number.
Founder & Principal Recruiter · Published October 30, 2026
How to tell if a candidate has actually run a liquid cooling loop
"Liquid cooling" now shows up on a lot of facilities resumes. These are the questions we use to find out who has done the work. Each one comes with what a strong answer includes.
Terms
| Term | Meaning |
|---|---|
| TCS | Technology cooling system. The loop through the CDU, rack manifolds and cold plates. |
| FWS | Facility water system. The building's chilled or condenser water, kept separate from the TCS by the CDU's heat exchanger. |
| PG25 | The standard cold plate coolant. 25% propylene glycol with corrosion inhibitors. |
| CDU | Coolant distribution unit. Pumps, a heat exchanger, filters and controls between the TCS and the FWS. |
Questions
What coolant runs in your TCS, and how do you check it?
Strong: PG25. Glycol checked with a refractometer and kept within 24.5 to 27.5%. pH within 8.0 to 10.5 (7.0 to 10.5 for OAT fluids). Samples sent out for lab analysis. Every inhibitor addition logged.
Red flag: "We top it off with water." Plain water dilutes the glycol and the inhibitors.
How fine are your CDU filters, and how do you know it's time to change them?
Strong: 25 or 50 micron. They watch differential pressure across the filter. Duplex filters let them swap an element without shutting down. Bonus if they know filtering too fine can strip the antifoam out of the coolant.
A turbidity sensor alarms. What do you check first?
Strong: whether it's air or debris. Turbidity sensors read air bubbles as particles. Air can mean a leak, or a hardware swap that wasn't purged. Then they check the buffer tank level.
Where do leaks actually happen on your loop?
Strong: at couplings, quick disconnects and joints, rarely the pipe itself. They can describe the rope sensors along the piping, spot sensors at the low point of drip pans, and a drop in tank level as an early sign. They check for mineral traces on visual rounds.
What happens to a loop that sits unused?
Strong: stagnant sections grow bacteria, which shifts pH and speeds up corrosion. They circulate and filter backup loops and unused feeders instead of leaving them idle.
Why not drop the chilled water setpoint to cool the chips harder?
Strong: condensation. When one plant serves both air and liquid loads, the water has to stay above dew point, which limits how low the setpoint can go.
Walk me through a fill and flush.
Strong: flush water clean enough to meet a conductivity limit (under 25 µS/cm in the OCP guideline), no biocides or soap in the final flush, then fill with PG25 within 24 hours. Uninhibited water never sits in the loop past a day.
A cold plate leaks inside a server. Who fixes it?
Strong: they know their site's responsibility split between the installer, the cooling vendor and the IT vendor, and when warranty terms mean they isolate and call instead of opening the server.
Red flags
- Can't name the coolant or its glycol percentage.
- Every answer is about CRAHs and air.
- Has never seen a fluid analysis report.
- Describes immersion tanks when you asked about cold plates. Fine for an immersion site, a gap for a direct-to-chip one.
Training
Schneider Electric's research team puts it plainly: facility teams know chilled water plants well, and distributing coolant to racks is still very new to most of them. What transfers straight across: chillers, pumps, hydronic balancing, BAS, and water treatment from cooling towers. What you'll teach: PG25 limits, quick disconnect handling, purging after hardware swaps, and where the vendor's responsibility starts.
We screen for all of this on every liquid cooling search.
Sources
- OCP PG25 Guidelines V1.0.0 (October 2026), Open Compute Project
- White Paper 210, Liquid Cooling System Challenges and Guidance, Schneider Electric
- PG25 Fluid Requirements Application Note, NVIDIA
Keep reading
Related work
Liquid cooling building engineer
What the job involves, BLS and posted pay, where the people come from, and the open roles.
Where liquid cooling technicians come from
Navy nuclear, hospital plants, pharma utilities, union trades and colo techs, with the gap each one has to close.
Liquid cooling roles
Register once and we contact you when a liquid cooling search opens in your market.

Czarina Tabayoyong
Founder and principal recruiter, Critical Path Hiring. Czarina recruits commissioning, MEP, power and critical facilities people for data center builds. She previously recruited cloud and data center architecture talent at AWS Professional Services, and PMO and project delivery talent for hyperscale data center campuses in Texas and Virginia.
Hiring call
Book a hiring call and we'll talk through which roles your build needs and when to bring them on.